c. Wiring - All necessary electrical connections should now be made.
• The Relay Unit is double insulated and does not require an earth connection.
• An earth connection block is provided on the backplate for terminating any cable
earth conductors.
• Earth continuity must be maintained and all bare earth conductors must be sleeved.
• Connect the Live mains feed to the backplate terminal labelled “L”.
• Connect the Neutral mains feed to the backplate terminal labelled “N”.
• If required, connect a loop of insulated wire between the Live terminal labelled “L”
and the relay Common terminal labelled “1”
• Ensure that no conductors are left protruding outside the central space enclosed by
the backplate.
• Refer to the diagram and table shown above for the wiring arrangement for a typi-
cal heating system. This diagram is schematic and should be used for guidance
only.
• Please ensure that all installations comply with the current IEE regulations.
• Please consult the heating system manufacturers installation instructions before
making these connections and note that a link may need to be removed when con-
necting external controls.
3. Fit Safety Cover - Check all of the wiring is safely attached to the appropriate back-
plate terminals and the screws are tight. Then fit the Safety Cover by clipping it into place over the wiring terminals.